Running Turbine
Running
- When the governing system assumes control, then adjust the speed fully open the emergency stop valve setting until the required speed, watching the turbinr speed following.
- Put into service the load as required.
- Make sure that bearing temperature is under 80C. When over 85 C, stop the turbine.
- Check the bearing oil pressure gauge to see that the bearing oil pressure is 0.7 - 1.5 kg/cm2 G.
- Adjust the supply of cooling water to the oil cooler to maintain oil temperature at outlet 30 - 50 C.
- Watch the turbine for unusual sounds and vibrations and take proper action if should occur.